A blend of two or more refrigerants that does not behave as a single pure substance. Boiling and condensation occur across a range of temperatures at constant pressure.
Temperature glide
Significant — typically 3–15°F (1.5–8°C). The dew point and bubble point differ at the same pressure.
Phase composition
Vapor and liquid phases have different compositions. More volatile component evaporates first.
Leak fractionation
Risk Partial vapor leak changes the remaining blend ratio — full recovery and recharge required.
Charging method
Liquid only — cylinder must be inverted to preserve blend composition. Never charge as vapor.
PT chart
Two-column table: one for bubble point (liquid) and one for dew point (vapor).
A blend that behaves exactly like a pure refrigerant at a specific composition. Vapor and liquid have the same composition at the boiling point.
Temperature glide
Zero (true azeotrope) or near-zero (<0.5°C for near-azeotropes). Single saturation temperature at any pressure.
Phase composition
Vapor and liquid maintain the same ratio — behaves as if it were a single-component fluid.
Leak fractionation
No risk Composition stays constant during a leak — no blend ratio change.
Charging method
Can be charged as liquid or vapor — composition remains constant either way.
PT chart
Single-column table — one saturation temperature per pressure, like a pure refrigerant.
ASHRAE 500-series
R-507A, R-500, R-502 (all obsolete or near-phaseout)
Why does temperature glide occur? — Core thermodynamic concept
In a zeotropic blend, the components have different vapor pressures (different volatilities). During evaporation, the more volatile component (lower boiling point — e.g. R-32 in R-407C) escapes to the vapor phase preferentially, leaving the liquid richer in the less volatile component. As the composition of the liquid changes, its boiling point changes too — so the temperature rises continuously from the bubble point (first bubble forms, liquid-rich) to the dew point (last droplet evaporates, vapor-rich). This rising temperature is the "glide."
In an azeotrope, at one specific mixture ratio, a unique thermodynamic interaction equalizes the effective vapor pressures of both components. At that composition, neither component can preferentially escape — vapor and liquid must have identical compositions. Result: zero glide, pure-fluid behavior.
Bubble point
Lower T
First bubble in liquid
Dew point
Higher T
Last droplet in vapor
Glide (zeotropic)
3–15°F
Dew minus bubble point
Glide (azeotropic)
< 0.5°F
Negligible / zero
Zeotropic — Temperature-Composition (T-x) Diagram
Two-phase envelope = region between bubble point (blue) and dew point (red) curves. Temperature glide = vertical gap between curves at any composition.
Curves converge and touch at the azeotropic composition — zero glide at that point. At other compositions, small glide exists.
Reading the diagram — key concepts
X-axis
Mole fraction of the higher-boiling-point component (0 = pure light component, 1 = pure heavy component).
Y-axis
Saturation temperature at constant pressure. Higher on the chart = higher temperature.
Blue curve
Bubble point — temperature at which the first bubble of vapor appears in a liquid mixture.
Red curve
Dew point — temperature at which the last droplet of liquid disappears in a vapor mixture.
Shaded region
Two-phase envelope — liquid and vapor coexist here. Operating in this region is normal for the evaporator and condenser.
Azeotrope point
Composition where both curves touch — minimum or maximum boiling point. Zero glide at this exact ratio.
Side-by-side property comparison
Property
Zeotropic Glide
Azeotropic No Glide
Temperature glide simulator — R-407C (zeotropic, 5.4°C glide)
Evaporating pressure:80 PSIG
Start of evaporation (bubble point)End of evaporation (dew point)
Bubble
Glide
Dew
32.0°FGlide: 9.7°F41.7°F
Blue = bubble point • Red = dew point • Green = temperature glide range
Practical impact of temperature glide in HVAC systems
Counterflow HX
When glide matches the secondary fluid's temperature rise in a counterflow heat exchanger, thermodynamic irreversibility decreases — efficiency improves.
Leak fractionation
Partial vapor leak releases preferentially the lighter component (R-32 from R-407C). The remaining charge becomes heavier — blend composition changes, requiring full recovery and recharge.
PT chart reading
Two-column PT charts: use the dew column for suction superheat; use the bubble column for liquid subcooling.
Superheat calc.
Always reference the dew point temperature at suction pressure for accurate superheat measurement in zeotropic blends.
Subcooling calc.
Always reference the bubble point temperature at discharge/liquid-line pressure for accurate subcooling measurement.
Retrofit consideration
Replacing R-22 with R-407C in existing equipment: the temperature glide affects evaporator performance — distributor orifices and TXV bulb position may need adjustment.