Zeotropic mixture is a refrigerant blend where the components have different boiling points and don’t behave as a single fluid. During evaporation or condensation at constant pressure, the temperature continuously changes — this is called temperature glide. The lighter component evaporates first, so the vapor and liquid phases always have different compositions. The practical consequence: if the system leaks, the remaining charge changes ratio (fractionation), and the technician must fully recover and recharge. Charging must always be done as liquid, with the cylinder inverted. R-407C, R-404A, R-448A, and R-454B are zeotropic.
Azeotropic mixture (non-zeotropic) is a blend that behaves exactly like a pure refrigerant at one specific composition. At that composition, vapor and liquid have identical makeup, so there is zero temperature glide — one single saturation temperature at any given pressure. No fractionation occurs during leaks, and the system can be charged as liquid or vapor. R-507A is the most common example, used as a near-perfect azeotrope in commercial refrigeration.
The widget has 5 tabs:
- Overview — definitions, key properties, charging rules
- Phase diagrams — T-x charts showing the two-phase envelope for both types
- Comparison table — side-by-side on 12 properties
- Temperature glide simulator — drag the pressure slider to see how bubble point, dew point, and glide change for R-407C
- Refrigerant examples — all 8 major blends with glide, GWP, composition, and practical notes